Sizing Guide Search

IQD20/IW126R Part Turn Isolating Combination

Output Performance
Combination Rated Torque Stroke Time Fail Safe
  Nm lbsft Secs (50 Hz)  
IQD20/IW126R 34000 25000 295.0 No
Available Output Flanges Available Enclosures Weight
(ISO5211 "F" & MSS SP-101 "FA") Hazardous Watertight Kg Lbs
F40/FA40, F48/FA48, F60/FA60 Yes Yes 1224.75 2700
Couplings
Coupling name Coupling Type Standard Dimension Max Dimension Min Dimension
mm in mm in mm in
IW MTW 12 13 Female Square 229 8.93 229 8.93 0 0.00
Actuator Performance
Size Rated Torque Output RPM Rating  
  Nm lbsft RPM (50Hz) Starts / Hour  
IQD20 136 100 36.00 60  
Available for power supply Available Enclosures Weight
1-Phase AC 3-Phase AC DC Hazardous Watertight Kg Lbs
No No DC 110V
Yes Yes 56.75 125
Handwheel Type Ratio Turns Rimpull
    (:1) (per stroke) N Lbsf
Standard Direct 1.0 177 632 142
Option 1 Geared 13.3 2354.1 231 52
Sales/Technical Information: IQD - Direct Current (DC)
Gearbox Performance
Size Rated Torque Ratio MA Weight
  Nm Lbsft (:1)   Kg Lbs
IW126R 180000 132761 708 250.0 1168.00 2575
Sales/Technical Information: IW Motorised

Enter your specific requirements and click ‘Add to enquiry’

Fields marked with an * are required.

« Go Back