Sizing Guide Search

CK60/IW126RA Part Turn Isolating Combination

Output Performance
Combination Rated Torque Stroke Time Fail Safe
  Nm lbsft Secs (50 Hz)  
CK60/IW126RA 101340 74316 2100.0 No
Available Output Flanges Available Enclosures Weight
(ISO5211 "F" & MSS SP-101 "FA") Hazardous Watertight Kg Lbs
F40/FA40, F48/FA48, F60/FA60 No Yes 1236.00 2725
Couplings
Coupling name Coupling Type Standard Dimension Max Dimension Min Dimension
mm in mm in mm in
IW MTW 12 13 Female Square 229 8.93 229 8.93 0 0.00
Warnings:
Stroke time over 600 seconds
Actuator Performance
Size Rated Torque Output RPM Rating  
  Nm lbsft RPM (50Hz) Starts / Hour  
CK60 60 44 36.00 60  
Available for power supply Available Enclosures Weight
1-Phase AC 3-Phase AC DC Hazardous Watertight Kg Lbs
No Yes No No Yes 33.00 73
Handwheel Type Ratio Turns Rimpull
    (:1) (per stroke) N Lbsf
Standard SSHW 10.0 12600 275 62
Gearbox Performance
Size Rated Torque Ratio MA Weight
  Nm Lbsft (:1)   Kg Lbs
IW126RA 180000 132761 5040 1689.0 1203.00 2652
Sales/Technical Information: IW Motorised

Enter your specific requirements and click ‘Add to enquiry’

Fields marked with an * are required.

« Go Back