Sizing Guide Search

IQTF125A Multi Turn Modulating Combination

Output Performance
Combination Rated Torque Modulating Torque Rated Thrust Resultant Thrust Stroke Time
  Nm lbsft Nm lbsft kN lbsf kN lbsf Secs (50 Hz)
IQTF125A 125 92 94 69.00 100.00 22480 0.00 0 0.0
Available Output Flanges Available Enclosures Weight Fail Safe
(ISO5210 "F" & MSS SP-102 "FA") Hazardous Watertight Kg Lbs  
F14/FA14 Yes Yes 20.00 46 No
Couplings
Coupling name Coupling Type Standard Dimension Max Dimension Min Dimension
mm in mm in mm in
A Thrust Base - Threaded 20 0.79 38 1.50 20 0.79
Warnings:
Actuator range has a limited number of turns/stroke length available.
Actuator Performance
Size Rated Torque Modulating Torque Output RPM Rating
  Nm lbsft Nm lbsft RPM (50Hz) Starts / Hour
IQTF125A 125 92 94 69 3.00 1200
Available for power supply Available Enclosures Weight
1-Phase AC 3-Phase AC DC Hazardous Watertight Kg Lbs
Yes Yes DC 24V
Yes Yes 20.00 46
Handwheel Type Ratio Turns Rimpull
    (:1) (per stroke) N Lbsf
Standard SSHW 120.0 - 38 8

Enter your specific requirements and click ‘Add to enquiry’

Fields marked with an * are required.